16区多线楼层复示器消防主机配套分重复显示器conventional repeater panel (出口英文版)
1.1 Product features
The panels have the following key features:
16 conventional repeater display zones.
1 Fire alarm output relay and 1 fault output relay .
1 Fire alarm output with 24VDC.
1 RS485 can be able to connect the other panel.
1.2 Specifications
Power supply: 16VDC to 30VDC
Current of power: Standby current: ≤15mA, Alarm current: ≤75mA
Relay contact capacity: 2A@24VDC
Buzzer level: 80dB@1m.
Protection level: IP55
Communication mode:RS485 (Wires: RVSP type,1.0MM2 to 2.0MM2)
Dimension of enclosure: 200mm(W)*91mm(H)*45mm(D)
Material of enclosure:ABS, White
Weight: 350g.
Hole of enter wires: 1/2 inch(12mm)
1.3 Repeater status indication and button operation
FIRE ALARM Status: When a fire alarm occurs, the corresponding zone red LED flashing and the internal
buzzer sounds. When “Silence” button pushed, the alarm zone LED lights steady and the buzzer silenced.
When another new fire alarm occurs, the new zone red LED flash and the buzzer sound again. In the fire
alarm status, the fire alarm “FIRE OUT” relay active and output “NO, NC, C” relay contacts and 24vdc power
output.
FAULT Status: When a fault event occurs, the corresponding zone’s yellow LED flashing and the internal
buzzer sounds. When “Silence” button pushed, the fault zone LED lights steady and the buzzer silenced.
When another new fault event occurs, the new zone yellow LED flash and the buzzer sound again. In the
fault alarm status, the fault alarm “FAULT OUT” relay active and output “NO, NC, C” relay contacts.
Normal status: When fire alarm panel’s fire or fault event restored, the fire alarm panel would send
commands to let the repeater to the Normal Status.
RUN LED: The “RUN” LED would keep light steady when the power supply in normal status.
COMM. LED: The “COMM.” LED would flash once about three to five seconds in normal communication
status.
SILENCE LED: In the fire or fault alarm status, press the “Silence” button the “SILENCE” LED would turn
on .
TEST LAMP: In normal status, press “TEST” button would have a lamp test.
SILENCE SOUND: In fire or fault status, press “SILENCE” button would silence the alarm sound.
RESET: In the “SILENCE” status,press “RESET” button once the repeater would return to the Normal
Status.